Troubleshooting of electrical system
This job was a troubleshooting job, which is more complicated because it needs more time to solve it. And time in shipping industry is not available. Also need to be experienced in this kind of job to solve it in time.
The problem was power failure in electronic panel– red diode lights while lifting hatch cover (31 tones). The hoisting capacity of the crane was 40 ton. While lifting less cargo (2 tones) there is no problem.
Started to check electrical side
I focused on the power supply part, measuring, and checking according to Maker Book. I found a loose wire on transformer side and I was thinking that this was the reason. But, the same failure occurred. Also I checked the DC part, measuring 24VDC and 8VDC circuits for electronics and other relays.
According to electrical schematic all power supply inside the crane 220VAC control voltage for main contactors, 24VDC and 8VDC for electronics and other relays is connection to the main 440VAC supply.
Service electrical system

If the main supply drops, the following events may occur (and the list is not complete):
- 24VDC supply dropping to 19 or 18VDC, electronic components malfunctioning (crane control is lost, not responding to joystick) or relays de-energizing (low oil level, high oil temperature, low feed pressure trip)
- 220VAC supply dropping to 160-170VAC, feed pump contactor, main Y/D unit contactors de-energizing (under load) with the consequent damage to contacts.
I found a loose electrical connection on the AC fuse of tri-phase transformer. One wire connection was loose and after re-tightening of the wire the DC voltage returned to 26 VDC.

[…] For more information, Part 2 is next […]